Delta 1.07 VFD-D D Instrukcja Użytkownika Strona 70

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 69
Chapter 4 Parameter Settings|DD Series
4-46
Settings
0: Disable
1: Enable
The door width will be difference due to its application. For example, the door of the freight elevator is
much wider than passenger elevator. Therefore, it needs to have door width auto tuning function to
measure the correct door width for the correct position and door open/close. This parameter is suitable
for the condition when door control mode is set to distance control mode (Pr.00-10=0).
The procedure for the door width auto-tuning function:
1. Close the door and make sure it reaches its close complete position, and then open the door to
measure the door width and close the door again to double check the door width.
2. After door width auto-tuning is complete, the measured value will write into Pr.03-12 and Pr.03-13
automatically.
Door close limit
0.0 %
Door open limit
100.0%
Close door (FWD)
Open door (REV)
Close door (FWD)
to make sure the position
of door close limit
measure door width
detect if door width is correct
Door Width Pulses (Unit:1)
Control mode
VF
VFPG SVC FOCPG FOCPM
Factory setting: 8800
Settings 1~9999
Door Width Pulses (Unit:10000)
Control mode
VF
VFPG SVC FOCPG FOCPM
Factory setting: 0
Settings 0~9999 (Unit:10000)
After door width auto tuning (Pr.03-11=1) is completed, door width pulses will write into Pr.03-12 and
Pr.03-13 automatically. User can also manually input door width pulses into Pr.03-12 and Pr.03-13.
Przeglądanie stron 69
1 2 ... 65 66 67 68 69 70 71 72 73 74 75 ... 140 141

Komentarze do niniejszej Instrukcji

Brak uwag