8-5 User Screen - Bottom Right
Option: Function:
Mains Frequency The average frequency measured on three
phases.
Motor kW The motor's running power in kilowatts.
Motor HP The motor's running power in horsepower.
Motor Temp The motor's temperature, calculated by the
thermal model.
kWh The number of kilowatt hours the motor has
run via the soft starter.
Hours Run The number of hours the motor has run via the
soft starter.
7.11.2 Performance Graphs
The loggings menu allows the user to view performance
information in real-time graphs.
The newest information is displayed at the right hand edge
of the screen. The graph can be paused to analyse data by
pressing and holding the OK button. To re-start the graph,
press and hold OK.
8-6 Graph Timebase
Option: Function:
Sets the graph time scale. The graph will progres-
sively replace the old data with new data.
10 secs
30 secs
1 min
5 minutes
10 minutes
30 minutes
1 hour
8-7 Graph Maximum Adjustment
Range: Function:
400%* [0% - 600%] Adjusts the upper limit of the performance
graph
8-8 Graph Minimum Adjustment
Range: Function:
0%* [0% - 600%] Adjusts the lower limit of the performance
graph.
8-9 Mains Reference Voltage
Range: Function:
400 V* [100 - 690
V]
Sets the nominal voltage for the LCP's
monitoring functions. This is used to
calculate motor kilowatts and kilovolt
amperes (kVA), but does not affect the MCD
500's motor control protection.
Enter the measured mains voltage.
7.12 Restricted Parameters
15-1 Access Code
Range: Function:
0000* [0000 -
9999]
Sets the access code to enter the simulation tools
and counter resets or the restricted section of the
Programming Menu (parameter group 15 and
higher).
Use the B
BACK
and O
OK
buttons to select which
digit to alter and use the
and
buttons to
change the value.
NOTE
In the event of a lost access code, contact
your supplier for master access code that
allows you to re-
program a new access
code.
15-2 Adjustment Lock
Option: Function:
Selects whether the LCP will allow parameters to be
changed via the Programming Menu.
Read &
Write
Allows users to alter parameter values in the
Programming Menu
Read Only Prevents users altering parameter values in the
Programming Menu. Parameter values can still be
viewed.
No Access Prevents users adjusting parameters in the
Programming Menu unless an access code is
entered.
NOTE
Changes to the Adjustment Lock setting take
effect only after the Programming Menu has
been closed.
15-3 Emergency Run
Option: Function:
Selects whether the soft starter will permit emergency run
operation. In emergency run, the soft starter will start (if
not already running) and continue to operate until
emergency run ends, ignoring stop commands and trips.
Emergency run is controlled using a programmable input.
When Emergency Run is activated in internally bypassed
models which are not running, the starter will attempt a
normal start while ignoring all trips. If a normal start is not
possible, a DOL start via the internal bypass relays will be
attempted. For non-bypassed models, an external
emergency run bypass contactor may be used.
15-4 Current Calibration
Range: Function:
100%* [85%
-
115%]
Motor Current Calibration calibrates the soft
starter's current monitoring circuits to match an
external current metering device.
Use the following formula to determine the
necessary adjustment:
Programming MCD 500 Operating Instruction
60 MG.17.K3.02 - VLT
®