Installation and
Maintenance
Instructions
KG / KGW Standard air-conditioning units
10/00 TV GB
Wolf GmbH · 84048 Mainburg · Postfach 1380 · Telefon 08751/74-0 · Telefax 08751/741600
Przeglądanie stron 0
1 2 3 4 5 6 ... 19 20

Podsumowanie treści

Strona 1 - Instructions

1Art.-Nr. 30 40 530Installation andMaintenanceInstructionsKG / KGW Standard air-conditioning units10/00 TV GBWolf GmbH · 84048 Mainburg · Postfach

Strona 2 - Contents

10Notes on installationThe weatherproofed KGW 630-1000 air-coinditioning units have a UV-resistant,weatherproof skinned roof.Fully assembled units are

Strona 3 - Notes on safety

11Notes on installationThe fan shaft must always be horizontal.Remember to remove the transportation locking devices of fans mounted onvibration dampe

Strona 4 - Standards

12When installing, take care to ensure that no dirt or other foreign matter penetrates insidethe washer.The water used for the washer under normal con

Strona 5

13CautionConnection to electricity supplyThe air-conditioning unit must be wired by a trained, qualified electrician inaccordance with the applicable

Strona 6

14Connecting to electricity supplyWiring for single-speed driveMotors up to 2.2 kW usually have direct startup,whereas a star-delta circuit is usual a

Strona 7

15CautionCautionInitial operationWait until the fan or fans run down to a complete standstill before you open theinspection door.Check that safety dev

Strona 8

16Air conditioner KG 15 20 25F 40F 40 63 100-1000Min. air flow (m³/h)550* 900 900 1600 1600 2500depends onhorizontal + vertical é designMin. air flow

Strona 9

17CautionInitial operationBefore filling the chiller system with refrigerant, adopt suitable measures to ensurethat no traces of moisture are left in

Strona 10 - Notes on installation

18CautionCautionMaintenanceBefore starting maintenance work, always switch off the main switch and repairswitch(es) and lock them in the OFF position.

Strona 11

19CautionCautionMaintenance / Frost protectionThe washer and drip separator must be cleaned at regular intervals. The cleaningcycle depends on the ope

Strona 12

2ContentsContents ... PageWarnings / Notes on safety ...

Strona 13

20Designation of equipment Airconditioning units for indoor installationAirconditioning units for outdoor installationAirconditioning units with indir

Strona 14 - Wiring for three-speed drive

3These Installation and Maintenance Instructions apply only to WOLF KG and KGWStandard air-conditioning units.The persons charged with the installatio

Strona 15 - Initial operation

4The standards and regulations applicable to the KG 15-250 Standard series andthe KG/KGW 630-1000 series air-conditioning units are as follows:- EC Di

Strona 16

5Delivery to site / TransportationDelivery to siteTransportClearancesKG 15-250 and KG/KWG 630-1000 series air conditioners are delivered to site intra

Strona 17

6Notes on installationFoundation Install the units and components on a surface which is smooth, level and ofadequate load-bearing strength.The base fr

Strona 18

7KG and KGW configurations incorporating a washer section require a base frameor foundation lower at the floor of the washer unit than elsewhere, beca

Strona 19

8Notes on installationSecuring the sections Sections with angle-section frames (KG 40-250) are secured by means of M6threaded fasteners and clip spac

Strona 20 - EC DECLARATION OF CONFORMITY

9Notes on installationConfigurations:stacked or side-by-sideSections for stacked configurations are delivered to site separately and must besecured to