The rated power of each engine-generator is limited by the
temperature, altitude and all other ambient conditions specified
by the engine manufacturer. Engine power will decrease 3-1/2%
for each 1000 ft. above sea level, and will decrease an additional
1% for each 10 degrees Fahrenheit above 60 degrees Fahren-
heit. Units should not be operated in ambient temperature greater
than 125 degrees Fahrenheit.
GENERATOR:
WINPOWER Generators Sets use totally brushless, AVR (Auto-
Voltage Regulator) controlled broad-range generator ends. The
generator converts rotational mechanical energy into electrical
energy. Standard WINPOWER units are equipped with genera-
tors manufactured by Stamford/Newage. Each generator ‘end’
has its own data tag. The unique serial number is stamped on the
data plate and into the upper section of the mounting adapter of
the generator frame. The data label is affixed to the main frame
of the generator on the lower left side, similar to the sample
shown.
ENGINE CONTROL PANEL LAYOUT
SPECIFICATIONS
GENERATOR SET:
Every WINPOWER Generator Set has its own unique identity data
plate. This data plate identifies the complete unit model number,
the system serial number and has links to the individual compo-
nents that form the generator set in our factory records. Several of
the major components also have their own individual identity plates
providing additional information to document build data for warranty
and replacement parts.
Be sure to have the main WINPOWER unit data plate information
recorded inside the front cover of this manual for future reference
and for identification whenever requesting field or factory technical
assistance. Sample data plate is shown for reference. Primary fields
needed for assistance are complete model number, serial number
and especially the M-Spec number. The M-Spec number (if pro-
vided) is recorded in the ‘TYPE NO.’ block on the Lower Right of the
plate. See the appendixes in the back of this manual for individual
units specifications and wiring diagram references.
ENGINE:
Each engine has a nameplate on it that gives the specific engine
model number, build specification and the serial number for the
engine. See the technical data pages in the back of this manual
for individual engine specifications, fuel consumptions and wiring
diagram references.
This manual covers specific operation of the combined engine
generator set. Refer to engine operating and maintenance
instructions for specific instruction on the care and maintenance
of the engine. Oil and fuel requirements along with maintenance
schedules and engine warranty information are provided by the
individual engine manufactures.
** CAUTION **
EQUIPMENT DAMAGE - Be sure to check the engine oil level
frequently as specified in the engine manual.
The engine manufacturer has established an excellent worldwide
engine service organization; engine service is available from a
nearby authorized dealer or distributor; check the Yellow Pages
of the telephone directory under “engines,” or ask the dealer from
whom you purchased the power plant.