VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-22
Group 4: Input Function Parameters
04 - 00
AVI Analog Input Bias
a Factory Setting: 0.00
Settings 0.00 to 200.00% Unit: 0.01%
04 - 01
AVI Bias Polarity
Factory Setting: 00
Settings 00 Positive Bias
01 Negative Bias
04 - 02
AVI Input Gain
a Factory Setting: 100
Settings 1 to 200% Unit: 1%
04 - 03
AVI Negative Bias, Reverse Motion Enabled
Factory Setting: 00
Settings 00 Forward motion only
01 Forward and reverse motion enabled. Forward motion with
positive bias. Reverse motion with negative bias.
02 Forward and reverse motion enabled. Forward and Reverse
motion with positive or negative bias. Select direction via the
keypad or external terminals.
04 - 11
ACI Analog Input Bias
a Factory Setting: 0.00
Settings 0.00 to 200.00% Unit: 0.01%
04 - 12
ACI Bias Polarity
Factory Setting: 00
Settings 00 Positive Bias
01 Negative Bias
04 - 13
ACI Input Gain
a Factory Setting: 100
Settings 01 to 200% Unit: 1%
04 - 14
ACI Negative Bias, Reverse Motion Enable
Factory Setting: 00
Settings 00 No ACI Negative bias command
01 Negative bias, REV motion enabled
02 Negative bias, REV motion disabled
04 - 15
AUI Analog Input Bias
a Factory Setting: 0.00
Settings 0.00 to 200.00% Unit: 0.01%
04 - 16
AUI Bias Polarity
Factory Setting: 00
Settings 00 Positive Bias
01 Negative Bias