DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming
communication. Set up the specific end word in D1167 and write the interruption subroutine I140.
When PLC receives the end word, the program will execute I140.
I150:
Communication instruction RS (COM2 RS-485) can be designated to send interrupt request when
specific charcters are received. Interrupt I150 and specific characters is set to low byte of D1168.
This function can be adopted when the PLC receives data of different length during the
communication. Set up the specific end word in D1168 and write the interruption subroutine I150.
When PLC receives the end word, the program will execute I150..
I160:
Communication instruction RS (COM3 RS-485) can be designated to send interrupt request when
specific charcters are received. Interrupt I160 and specific characters is set to low byte of D1169
This function can be adopted when the PLC receives data of different length during the
communication. Set up the specific end word in D1169 and write the interruption subroutine I160.
When PLC receives the end word, the program will execute I160