Delta D25886 Instrukcja Użytkownika Strona 77

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 76
4. Motion Control Instructions
4-36 DVP-MC operating manual
4.4.8. MC_Power
API
Controller
08
MC_Power
Power control instruction
10MC11T
Explanation of the Instruction:
MC_Power is applied to enable or disable the corresponding servo axis.
Explanation of input and output parameter of the instruction:
Parameter
name
Explanation
Data
type
Available
device
Axis The node address of servo drive UINT
Constant,
D
Enable “Enable” turns Off –> On, this instruction is executed BOOL
M,I,Q,
Constant
AxisStart
When “AxisStart” turns on, “Enable” turns Off –> On and servo
drive is enabled;
When “AxisStart” turns off , “Enable” turns Off –> On and servo
drive is disabled
BOOL
M,I,Q,
Constant
Status
“Status” turns on after axis is enabled; if “Enable” is off,
“Status” is reset.
BOOL M,Q
Error
If any error is detected, "Error" turns on; when “Enable” turns
On –> Off, "Error" is reset.
BOOL M,Q
ErrorID Error code. Please refer to section 5.3. UINT D
Note:
1. Axis can not be powered off or powered on as servo motor is running. At this moment, if "
Power
Off/On" action is performed, "Error" will turn on, but servo drive will not be impacted at all.
2. The motion control instructions can control the axis to do the corresponding motion after servo axis is
powered on. Except for the virtual axis, all motion control instructions can not be executed when axis
is powered off.
Przeglądanie stron 76
1 2 ... 72 73 74 75 76 77 78 79 80 81 82 ... 338 339

Komentarze do niniejszej Instrukcji

Brak uwag