Title page
GE Multilin's Quality
Management System is
registered to ISO9001:2000
QMI # 005094
GE Digital Energy
Multilin
GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222 Fax: (905) 201-2098
Internet: http://www.GEmultilin.com
Instruction manual
MM300 revision: 1.31
Manual P/N: 1601-9023-A6
GE publication code: GEK-113022E
Copyright © 2008 GE Multilin
IISO9001:2000
G
E
M
U
L
T
I
L
I
N
R
E
G
I
S
T
E
R
E
D
*1601-9023-A6*
MM300
Motor Management System
Low voltage motor protection and control
Przeglądanie stron 0
1 2 3 4 5 6 ... 166 167

Podsumowanie treści

Strona 1 - Motor Management System

LISTED52TLIND.CONT. EQ.E83849Title pageGE Multilin's Quality Management System is registered to ISO9001:2000QMI # 005094GE Digital EnergyMultilin

Strona 2

1–4 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALOVERVIEW CHAPTER 1: INTRODUCTIONFigure 3: MM300 feature overview1.1.3 MM300 order codesThe info

Strona 3 - Table of Contents

CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–13CT Primary (Mandatory Setpoint)Range: 5 to 1000 amp

Strona 4

6–14 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONFIGURATION SETPOINTS CHAPTER 6: SETPOINTS6.2.3 InputsThe MM300 digital (contact) inputs are

Strona 5

CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–15– “Forward Limit”: This value represents a contact

Strona 6

6–16 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONFIGURATION SETPOINTS CHAPTER 6: SETPOINTSThe terminal designation is indicated under the “Te

Strona 7 - Chapter 1: Introduction

CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–17Figure 14: Output configuration setpoints control p

Strona 8

6–18 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONFIGURATION SETPOINTS CHAPTER 6: SETPOINTSNOTENOTE: Stop A and Stop B are not included in the

Strona 9 - Figure 2: Single line diagram

CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–19NOTENOTE: When changing the IP address, power to th

Strona 10 - 1.1.3 MM300 order codes

6–20 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONFIGURATION SETPOINTS CHAPTER 6: SETPOINTS6.2.6 SystemFigure 17: System setpoint pageThe fol

Strona 11

CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–21Set TimeSet to program current time.Time Offset fro

Strona 12 - 1.2 Specifications

6–22 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONFIGURATION SETPOINTS CHAPTER 6: SETPOINTSPhasor DisplayRange: Leading, LaggingDefault: Laggi

Strona 13

CHAPTER 1: INTRODUCTION OVERVIEWMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 1–51.1.4 Example of an MM300 order codeMM300GEHS1CAXXXX: MM300 wit

Strona 14 - 1.2.5 Inputs specifications

CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–236.2.8 WaveformsFigure 19: Waveform setpoint pageTh

Strona 15

6–24 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONFIGURATION SETPOINTS CHAPTER 6: SETPOINTSSample RateRange: 1 cycle, 1 second, 1 minute, 1 ho

Strona 16 - 1.2.6 Outputs specifications

CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–25Drive Greasing IntevalRange: 100 to 50000 hours in

Strona 17 - DIMENSIONS

6–26 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPROTECTION ELEMENTS CHAPTER 6: SETPOINTS6.3 Protection elements6.3.1 Thermal protectionThe pr

Strona 18 - OPERATING ENVIRONMENT

CHAPTER 6: SETPOINTS PROTECTION ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–27• Ieq represents the equivalent motor heating current i

Strona 19

6–28 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPROTECTION ELEMENTS CHAPTER 6: SETPOINTSThe MM300 calculates the steady-state thermal capacity

Strona 20 - Chapter 2: Installation

CHAPTER 6: SETPOINTS PROTECTION ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–296.3.1.4 Overload curveThe overload curve accounts for

Strona 21 - 2.1.3 Mounting

6–30 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPROTECTION ELEMENTS CHAPTER 6: SETPOINTSFigure 24: Standard overload curvesThe trip times for t

Strona 22 - CAUTION:

CHAPTER 6: SETPOINTS PROTECTION ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–31Table 1: Standard overload curve trip times (in seconds

Strona 23 - Figure 5: DIN rail mounting

6–32 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPROTECTION ELEMENTS CHAPTER 6: SETPOINTSFigure 25: Thermal model cooling following a trip at t

Strona 24 - 853727A1.CDR

1–6 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALSPECIFICATIONS CHAPTER 1: INTRODUCTION1.2 SpecificationsNOTENOTE: Specifications are subject to

Strona 25 - 853734A1.CDR

CHAPTER 6: SETPOINTS PROTECTION ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–33Figure 26: Thermal protection configuration setpointsTh

Strona 26

6–34 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPROTECTION ELEMENTS CHAPTER 6: SETPOINTSRTD Bias - Center TRange: 0 to 250°C in steps of 1 or O

Strona 27

CHAPTER 6: SETPOINTS PROTECTION ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–356.3.2 Mechanical protectionSelect the Home > Setpoi

Strona 28 - 2.2.2 CPU module

6–36 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPROTECTION ELEMENTS CHAPTER 6: SETPOINTS6.3.2.2 Undercurrent protectionWhen the motor is in th

Strona 29

CHAPTER 6: SETPOINTS PROTECTION ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–37Underpower Trip LevelRange: 1 to 100% MNR in steps of 1

Strona 30

6–38 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPROTECTION ELEMENTS CHAPTER 6: SETPOINTS6.3.3 Electrical protection6.3.3.1 Current unbalance

Strona 31 - 853745A1.CDR

CHAPTER 6: SETPOINTS PROTECTION ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–39NOTENOTE: The ground fault protection pickup setpoints

Strona 32 - 2.2.3 Protection modules

6–40 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPROTECTION ELEMENTS CHAPTER 6: SETPOINTS6.3.3.3 Load increase alarmThe load increase alarm is

Strona 33 - Core Balance (Zero Sequence)

CHAPTER 6: SETPOINTS PROTECTION ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–41Undervoltage Trip DelayRange: 1 to 60 seconds in steps

Strona 34 - 2.2.3.2 Two CT configuration

6–42 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPROTECTION ELEMENTS CHAPTER 6: SETPOINTSThe following setpoints are available for the phase ove

Strona 35 - FUSES - 100 ma typical

CHAPTER 1: INTRODUCTION SPECIFICATIONSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 1–7MECHANICAL JAMPickup level:...

Strona 36 - 2.2.4 Input/output modules

CHAPTER 6: SETPOINTS PROTECTION ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–43VT Fuse FailRange: Disabled, Alarm, TripDefault: TripTh

Strona 37

6–44 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPROTECTION ELEMENTS CHAPTER 6: SETPOINTSAll RTDs programmed with an alarm or a trip are monitor

Strona 38

CHAPTER 6: SETPOINTS PROTECTION ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–45Cold ResistanceRange: 0.1 to 30.0 kOHMS in steps of 0.1

Strona 39 - Multilin

6–46 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONTROL ELEMENTS CHAPTER 6: SETPOINTS6.4 Control elements6.4.1 Starter setpointsSelect the Ho

Strona 40 - 2.3 Starter types

CHAPTER 6: SETPOINTS CONTROL ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–47The auto/manual control element includes non-volatile latc

Strona 41 - Low Voltage

6–48 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONTROL ELEMENTS CHAPTER 6: SETPOINTSHard Wired 2W/3WRange: 2W, 3WDefault: 3WThe setpoint is fo

Strona 42 - 2.3.3 Two-speed starter

CHAPTER 6: SETPOINTS CONTROL ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–49Test Manual ModeRange: On, Off, UnaffectedDefault: OnWhen

Strona 43

6–50 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONTROL ELEMENTS CHAPTER 6: SETPOINTSIf an A or B motor contactor is externally energized, the

Strona 44

CHAPTER 6: SETPOINTS CONTROL ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–51The starts per hour element defines the number of start at

Strona 45

6–52 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONTROL ELEMENTS CHAPTER 6: SETPOINTSStarts/Hour LimitRange: 1 to 5 in steps of 1 or OFFDefault

Strona 46

1–8 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALSPECIFICATIONS CHAPTER 1: INTRODUCTION1.2.2 User interface specificationsGRAPHICAL CONTROL PANE

Strona 47

CHAPTER 6: SETPOINTS CONTROL ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–53Figure 30: Process interlock timingThe following setpoints

Strona 48 - 2.3.6 Soft starter type

6–54 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONTROL ELEMENTS CHAPTER 6: SETPOINTSIL A Startup OverrideRange: 0 to 3600 seconds in steps of

Strona 49

CHAPTER 6: SETPOINTS CONTROL ELEMENTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–55If the motor was not running at the start of the dip, no r

Strona 50

6–56 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONTROL ELEMENTS CHAPTER 6: SETPOINTSUVR Med Dip TimeRange: 0.1 to 10.0 s in steps of 0.1 secon

Strona 51 - 3.1.1.1 Graphical display

CHAPTER 6: SETPOINTS SYSTEM SECURITYMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–576.5 System securityHardware and passcode security features

Strona 52 - 3.1.1.2 Keypad

6–58 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALSYSTEM SECURITY CHAPTER 6: SETPOINTSPasscode Level 1, Passcode Level 2, Passcode Level 3Range:

Strona 53

MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 7–1MM300 Motor Management SystemChapter 7: DiagnosticsDigital EnergyMultilinDiagnosti csThe diagnos

Strona 54 - 3.1.1.4 LED indicators

7–2 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALEVENTS CHAPTER 7: DIAGNOSTICSIndividual events are selected by using the UP and DOWN keys to hig

Strona 55 - Level 1 Level 2 Level 3

CHAPTER 7: DIAGNOSTICS DIGITAL COUNTERSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 7–37.2 Digital countersThe Home > Diag > Counters pag

Strona 56 - 3.1.2.3 Actual values pages

7–4 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALDIGITAL COUNTERS CHAPTER 7: DIAGNOSTICSMotor Stopped HoursRange: 0 to 100000 hours in steps of 1

Strona 57 - 3.1.2.4 Status pages

CHAPTER 1: INTRODUCTION SPECIFICATIONSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 1–9GROUND CURRENT INPUT (50:0.025)CT primary:...

Strona 58

CHAPTER 7: DIAGNOSTICS PHASORSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 7–57.3 PhasorsThe Home > Diag > Phasors page displays phase vo

Strona 59 - 3.1.2.5 Setpoints pages

7–6 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPRODUCT INFORMATION CHAPTER 7: DIAGNOSTICS7.4 Product informationThe Home > Diag > Info p

Strona 60 - 3.1.2.6 Diagnostics pages

CHAPTER 7: DIAGNOSTICS LEARNED DATAMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 7–77.5 Learned dataThe Home > Diag > Learned page display

Strona 61 - 3.1.2.8 Popup windows

7–8 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALWAVEFORM CHAPTER 7: DIAGNOSTICS7.6 WaveformThe Home > Diag > Waveform page displays the M

Strona 62

CHAPTER 7: DIAGNOSTICS DATALOGMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 7–97.7 DatalogThe Home > Diag > Datalog page displays the MM30

Strona 63 - 3.1.3.2 Numeric setpoints

7–10 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALDATALOG CHAPTER 7: DIAGNOSTICS

Strona 64

MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 8–1MM300 Motor Management SystemChapter 8: FlexLogic™Digital EnergyMultilinFlexLogic ™8.1 FlexLogi

Strona 65 - 3.1.3.5 Security access

8–2 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALFLEXLOGIC™ OVERVIEW CHAPTER 8: FLEXLOGIC™• Each timer may only be used once within any given sta

Strona 66 - 3.2 Basic control panel

CHAPTER 8: FLEXLOGIC™ FLEXLOGIC™ OVERVIEWMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 8–3Comm Trip... Asserted whe

Strona 67

8–4 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALFLEXLOGIC™ OVERVIEW CHAPTER 8: FLEXLOGIC™MCC Stop ...Asserted w

Strona 68 - Chapter 4: Software operation

1–10 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALSPECIFICATIONS CHAPTER 1: INTRODUCTION1.2.6 Outputs specificationsOUTPUT RELAYSConfiguration:

Strona 69 - 4.1.1 Software requirements

CHAPTER 8: FLEXLOGIC™ FLEXLOGIC™ OVERVIEWMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 8–5Protection operands: overvoltageOvervoltage Alarm ...

Strona 70

8–6 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALFLEXLOGIC™ OVERVIEW CHAPTER 8: FLEXLOGIC™Contactor Inspect Alarm...Asserted when the number of

Strona 71 - USB port:

MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 9–1MM300 Motor Management SystemChapter 9: CommunicationsDigital EnergyMultilinCommunicatio ns9.1

Strona 72

9–2 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCOMMUNICATIONS INTERFACES CHAPTER 9: COMMUNICATIONS

Strona 73

MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL a–1MM300 Motor Management SystemAppendixGE Digital EnergyMultilinAppendixA.1 Change notesA.1.1 Ma

Strona 74

a–2 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALAPPENDIX6.2.4 Drive Available setpoint added6.3.3.5 Note added re Aux Undervoltage8.1.1Flexlogic

Strona 75

APPENDIXMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL a–3Ch5 - Status Misc. Setpoints addedCh5 - UV Autorestart Two NOTES added - end of setpoint

Strona 76 - 4.2 Power analysis

a–4 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALAPPENDIX

Strona 77

CHAPTER 1: INTRODUCTION SPECIFICATIONSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 1–11USB PORT (GRAPHIC CONTROL PANEL ONLY)Standard specificati

Strona 78

1–12 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALSPECIFICATIONS CHAPTER 1: INTRODUCTION1.2.11 Environmental specificationsOPERATING ENVIRONMENT

Strona 79 - 4.2.2 Data logger

CHAPTER 1: INTRODUCTION SPECIFICATIONSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 1–13

Strona 80

© 2008 GE Multilin Incorporated. All rights reserved.GE Multilin MM300 Motor Management System instruction manual for revision 1.31.MM300 Motor Manage

Strona 81

MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–1MM300 Motor Management SystemChapter 2: InstallationDigital EnergyMultilinInstal lation2.1 Mech

Strona 82 - Chapter 5: Actual values

2–2 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALMECHANICAL INSTALLATION CHAPTER 2: INSTALLATIONFigure 1: MM300 dimensions2.1.2 Product identifi

Strona 83 - 5.2 Metering

CHAPTER 2: INSTALLATION MECHANICAL INSTALLATIONMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–3Figure 3: Panel mounting and cutout dimensionsThe

Strona 84 - 5.2.4 Sensor metering

2–4 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALMECHANICAL INSTALLATION CHAPTER 2: INSTALLATIONFigure 4: Basic Control Panel mounting and cutout

Strona 85 - 5.3 Status

CHAPTER 2: INSTALLATION MECHANICAL INSTALLATIONMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–5The screw mount for high vibration environments i

Strona 86 - 5.3.4 Flex Page

2–6 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALMECHANICAL INSTALLATION CHAPTER 2: INSTALLATIONFigure 7: Removing a module from the MM300Use the

Strona 87

CHAPTER 2: INSTALLATION MECHANICAL INSTALLATIONMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–7The MM300 terminals are labeled with a three-char

Strona 88 - Chapter 6: Setpoints

2–8 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION2.2 Electrical installationThis section describe

Strona 89

CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATIONMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–9NOTENOTE: It is recommended that you install a ci

Strona 90 - 6.2 Configuration setpoints

2–10 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALELECTRICAL INSTALLATION CHAPTER 2: INSTALLATIONFigure 11: CBCT connectionCAUTIONCAUTION: The ze

Strona 91

MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL toc–iTable of Contents1. INTRODUCTION Overview ...

Strona 92 - Wye-Delta Starter

CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATIONMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–11Figure 12: Core balance ground CT installation,

Strona 93 - 853717A1.CDR

2–12 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION2.2.2.2 Thermistor connectionsEither a positive

Strona 94 - 6.2.1.4 Two-speed starter

CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATIONMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–13One two-wire RS485 port is provided. Up to 32 MM

Strona 95 - 853719A1.CDR

2–14 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION2.2.3.1 Phase current inputs (IO_A module)Figur

Strona 96 - 6.2.1.6 Inverter starter

CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATIONMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–152.2.3.2 Two CT configurationEach of the two CTs

Strona 97 - 853721A1.CDR

2–16 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION2.2.3.3 Phase voltage inputs (IO_B module)The M

Strona 98 - 6.2.1.7 Soft starter

CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATIONMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–172.2.3.4 RTD sensor connections (I0_G module)The

Strona 99

2–18 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION2.2.4.1 Type IO_C module connectionsFigure 22:

Strona 100

CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATIONMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–192.2.4.2 Type IO_D module connectionsThe IO_D mo

Strona 101 - 6.2.3 Inputs

2–20 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION2.2.5 Dielectric strength testingFigure 24: Tes

Strona 102 - 6.2.4 Outputs

toc–ii MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALTroubleshooting the USB driver ...

Strona 103

CHAPTER 2: INSTALLATION STARTER TYPESMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–212.3 Starter types2.3.1 Full-voltage non-reversing starte

Strona 104

2–22 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALSTARTER TYPES CHAPTER 2: INSTALLATION2.3.2 Full-voltage reversing starterFigure 26: Full-volta

Strona 105

CHAPTER 2: INSTALLATION STARTER TYPESMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–232.3.3 Two-speed starterFigure 27: Two-speed starter typic

Strona 106

2–24 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALSTARTER TYPES CHAPTER 2: INSTALLATIONNOTENOTE: Connect AUX VT to the Control Supply for correct

Strona 107 - 6.2.6 System

CHAPTER 2: INSTALLATION STARTER TYPESMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–252.3.4 Wye-delta open transition starterFigure 28: Wye-del

Strona 108

2–26 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALSTARTER TYPES CHAPTER 2: INSTALLATIONNOTENOTE: Connect AUX VT to the Control Supply for correct

Strona 109 - 6.2.7 Events

CHAPTER 2: INSTALLATION STARTER TYPESMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–272.3.5 Inverter starter (VFD, VSD)Figure 29: Inverter star

Strona 110 - 6.2.9 Datalog

2–28 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALSTARTER TYPES CHAPTER 2: INSTALLATIONForced starts (for example, External Start) operate in the

Strona 111 - 6.2.10 Counters

CHAPTER 2: INSTALLATION STARTER TYPESMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 2–292.3.6 Soft starter typeFigure 30: Soft starter typical wi

Strona 112

2–30 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALSTARTER TYPES CHAPTER 2: INSTALLATIONNOTENOTE: Ensure soft starter is located before contactor.

Strona 113 - 6.3.1.1 Unbalance biasing

MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL toc–iii8. FLEXLOGIC™ FlexLogic™ overview...

Strona 114 - 6.3.1.2 Hot/cold biasing

MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 3–1MM300 Motor Management SystemChapter 3: Control panel operationDigital EnergyMultilinControl pa

Strona 115 - 6.3.1.3 RTD biasing

3–2 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALGRAPHICAL CONTROL PANEL CHAPTER 3: CONTROL PANEL OPERATIONFigure 1: MM300 front panel with examp

Strona 116 - 6.3.1.4 Overload curve

CHAPTER 3: CONTROL PANEL OPERATION GRAPHICAL CONTROL PANELMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 3–3The remainder of the screen shows the

Strona 117 - TIME IN SECONDS

3–4 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALGRAPHICAL CONTROL PANEL CHAPTER 3: CONTROL PANEL OPERATION• When a field is open for editing, th

Strona 118 - 6.3.1.5 Cooling rate

CHAPTER 3: CONTROL PANEL OPERATION GRAPHICAL CONTROL PANELMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 3–5Pressing an invalid key displays a mes

Strona 119 - Time (minutes)

3–6 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALGRAPHICAL CONTROL PANEL CHAPTER 3: CONTROL PANEL OPERATION3.1.2 MM300 graphical display pagesA

Strona 120

CHAPTER 3: CONTROL PANEL OPERATION GRAPHICAL CONTROL PANELMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 3–73.1.2.1 Home display pageThe home pag

Strona 121 - RTD Bias – Center T

3–8 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALGRAPHICAL CONTROL PANEL CHAPTER 3: CONTROL PANEL OPERATION• Sensor (metered temperature and ther

Strona 122 - 6.3.2.1 Mechanical jam

CHAPTER 3: CONTROL PANEL OPERATION GRAPHICAL CONTROL PANELMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 3–9• Message (displays all locked out con

Strona 123

3–10 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALGRAPHICAL CONTROL PANEL CHAPTER 3: CONTROL PANEL OPERATION3.1.2.5 Setpoints pagesThe setpoints

Strona 124

toc–iv MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

Strona 125 - 6.3.3 Electrical protection

CHAPTER 3: CONTROL PANEL OPERATION GRAPHICAL CONTROL PANELMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 3–113.1.2.6 Diagnostics pagesThe diagnos

Strona 126 - Ground CT setpoint

3–12 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALGRAPHICAL CONTROL PANEL CHAPTER 3: CONTROL PANEL OPERATIONFigure 16: Typical event diagnosis pa

Strona 127 - 6.3.3.4 Phase undervoltage

CHAPTER 3: CONTROL PANEL OPERATION GRAPHICAL CONTROL PANELMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 3–13Figure 18: Typical help popup windowI

Strona 128 - 6.3.3.6 Phase overvoltage

3–14 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALGRAPHICAL CONTROL PANEL CHAPTER 3: CONTROL PANEL OPERATION3. Press the ENTER key. A popup windo

Strona 129 - 6.3.3.8 Fuse failure

CHAPTER 3: CONTROL PANEL OPERATION GRAPHICAL CONTROL PANELMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 3–15Otherwise, an error statement is disp

Strona 130 - 6.3.4.1 RTD protection

3–16 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALGRAPHICAL CONTROL PANEL CHAPTER 3: CONTROL PANEL OPERATION3.1.3.4 Date, time, and IP entryThe

Strona 131

CHAPTER 3: CONTROL PANEL OPERATION BASIC CONTROL PANELMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 3–173.2 Basic control panelThe MM300 basic c

Strona 132

3–18 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALBASIC CONTROL PANEL CHAPTER 3: CONTROL PANEL OPERATION

Strona 133 - 6.4.1.1 Auto/manual control

MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 4–1MM300 Motor Management SystemChapter 4: Software operationDigital EnergyMultilinSoftware opera

Strona 134

4–2 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALENERVISTA MM300 SETUP SOFTWARE CHAPTER 4: SOFTWARE OPERATION4.1.1 Software requirementsThe foll

Strona 135 - Start Ctrl

MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 1–1MM300 Motor Management SystemChapter 1: IntroductionDigital EnergyMultilinIntroductionPlease rea

Strona 136 - External Stop Action

CHAPTER 4: SOFTWARE OPERATION ENERVISTA MM300 SETUP SOFTWAREMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 4–36. EnerVista Launchpad will obtain t

Strona 137 - 6.4.2 Starting duty inhibits

4–4 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALENERVISTA MM300 SETUP SOFTWARE CHAPTER 4: SOFTWARE OPERATIONIf you are going to communicated fro

Strona 138

CHAPTER 4: SOFTWARE OPERATION ENERVISTA MM300 SETUP SOFTWAREMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 4–512. Select No, not this time.The abo

Strona 139 - 6.4.3 Process interlocks

4–6 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALENERVISTA MM300 SETUP SOFTWARE CHAPTER 4: SOFTWARE OPERATION3. Check the Setup Software for the

Strona 140 - 853703A1.CDR

CHAPTER 4: SOFTWARE OPERATION ENERVISTA MM300 SETUP SOFTWAREMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 4–75. If problem still persists, uninst

Strona 141 - IL Function A setpoint

4–8 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALENERVISTA MM300 SETUP SOFTWARE CHAPTER 4: SOFTWARE OPERATION8. Select Install the software autom

Strona 142

CHAPTER 4: SOFTWARE OPERATION POWER ANALYSISMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 4–94.2 Power analysis4.2.1 Waveform captureThe EnerVi

Strona 143

4–10 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPOWER ANALYSIS CHAPTER 4: SOFTWARE OPERATION6. The red vertical line indicates the trigger poin

Strona 144 - 6.5 System security

CHAPTER 4: SOFTWARE OPERATION POWER ANALYSISMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 4–1110. Change the color of each graph as desired, and

Strona 145

4–12 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPOWER ANALYSIS CHAPTER 4: SOFTWARE OPERATION12. Use the graph attribute utility described in st

Strona 146 - Chapter 7: Diagnostics

1–2 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALOVERVIEW CHAPTER 1: INTRODUCTIONFigure 1: Note icons used in the documentationThe standard note

Strona 147 - EVENTS CHAPTER 7: DIAGNOSTICS

CHAPTER 4: SOFTWARE OPERATION POWER ANALYSISMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 4–137. The method of customizing the datalog view is th

Strona 148 - 7.2 Digital counters

4–14 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALPOWER ANALYSIS CHAPTER 4: SOFTWARE OPERATION

Strona 149

MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 5–1MM300 Motor Management SystemChapter 5: Actual valuesDigital EnergyMultilinActual values5.1 Act

Strona 150 - 7.3 Phasors

5–2 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALMETERING CHAPTER 5: ACTUAL VALUES5.2 Metering5.2.1 Current meteringSelect the Values > Amps

Strona 151 - 7.4 Product information

CHAPTER 5: ACTUAL VALUES METERINGMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 5–35.2.3 Power meteringSelect the Values > Power page to displ

Strona 152 - 7.5 Learned data

5–4 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALSTATUS CHAPTER 5: ACTUAL VALUES5.3 StatusThe MM300 status messages are categorized as trip, ala

Strona 153 - 7.6 Waveform

CHAPTER 5: ACTUAL VALUES STATUSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 5–5Figure 7: Typical input status message page5.3.3 System PageShow

Strona 154 - 7.7 Datalog

5–6 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALSTATUS CHAPTER 5: ACTUAL VALUES

Strona 155

MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–1MM300 Motor Management SystemChapter 6: SetpointsDigital EnergyMultilinSetpoint s6.1 Understand

Strona 156 - Chapter 8: FlexLogic™

6–2 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALUNDERSTANDING SETPOINTS CHAPTER 6: SETPOINTSThe pages containing setpoint fields, except for the

Strona 157

CHAPTER 1: INTRODUCTION OVERVIEWMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 1–3Figure 2: Single line diagramTable 1: MM300 protection functions

Strona 158

CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–36.2 Configuration setpointsThe configuration setpoi

Strona 159

6–4 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONFIGURATION SETPOINTS CHAPTER 6: SETPOINTSMotor NameRange: up to 20 alphanumeric charactersDef

Strona 160

CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–5Figure 3: Typical starter timingThe following sectio

Strona 161

6–6 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONFIGURATION SETPOINTS CHAPTER 6: SETPOINTS6.2.1.2 Full-voltage non-reversing starterIf the St

Strona 162 - Chapter 9: Communications

CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–7Figure 5: Typical starter timing for full-voltage re

Strona 163

6–8 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONFIGURATION SETPOINTS CHAPTER 6: SETPOINTSFigure 6: Typical starter timing for two-speed start

Strona 164 - Appendix

CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–9Pre-contactor is omitted on forced starts (for examp

Strona 165 - Section Number CHANGES

6–10 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONFIGURATION SETPOINTS CHAPTER 6: SETPOINTSForced starts (for example, external start) operate

Strona 166

CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTSMM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–11Ramp Down TimeRange: 0 to 125 seconds in steps of 1

Strona 167

6–12 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUALCONFIGURATION SETPOINTS CHAPTER 6: SETPOINTSPre-Contactor TimeRange: 0 to 60 seconds in steps o

Komentarze do niniejszej Instrukcji

Brak uwag