MMC120 Linear Motion Control Module Overview
Delta Computer Systems, Inc. 360/254-8688 11
SPECIFICATIONS
Temperature
Operating: 0
o
Cto+60
o
C
Storage: -40
o
Cto+85
o
C
Humidity
93% non-condensing
Vibration Resistance
1gat60Hzto500Hzfor23minutes
0.075 mm displacement from 10 Hz to 60 Hz
Shock Resistance
30 g for 11 milliseconds
ESD Immunity
8kV
Power Requirements
+5V @ 1 Amp from the backplane
Transducer Inputs
Direct interface to magnetostrictive transducers
Differential or single-ended transducer compatibility
Start/Stop pulses or Pulse Width Modulated signals
Outputs
±10 volts into 2000 Ohm or greater load -- current output is available with the optional VC2100 voltage-to-
current converter
Isolation
All inputs and outputs used for control purposes are optically isolated from the module, with 2500VDC
withstand voltage
Each input and output section is isolated from the other sections
The RS-232 port is not isolated
I/O Protection
All inputs and outputs are protected against transients by clamp diodes
Agency Compliance
UL, CSA, and CE